ECA030: NETFINITY RACK (M/T9306) SIDE PANELS TOO HIGH


Subject: ECA030: NETFINITY RACK (M/T9306) SIDE PANELS TOO HIGH
New Netfinity server RETAIN ECA030: 

    Record number:       H166483
    Device:              D/T9306         Service code:      33
    ECA number:          ECA030          Parts source:      LOC
    EC number:           EC000000        Publish flag:      R
    Mandatory:           N               Hit count:         UHC00000
    Automatic shipment:  N               Success count:     USC0000
    Availability date:   99/03           Publication code:  PC50
    Plant of control:    23              Date created:      O99/03/15
    Tip key:                             Date last altered: A99/05/11
                                         Owning B.U.:       USA


Abstract: ECA030: NETFINITY RACK (M/T9306) SIDE PANELS TOO HIGH


PURPOSE:

This ECA provides for the replacement of a side panel in a limited number of Netfinity Rack systems.

This is NOT a mandatory ECA.

To order this ECA, contact your IBM Branch Office, Central Response Office or Designated Country ECA Coordinator.
This ECA is scheduled to be withdrawn April 30, 2000.

  FEATURES:
  Type,                  Machines Affected
  Model,   With          and/or Feature/Device     B/M to be    Service  System
  Stage    B/M           Description               Installed    Hours    Hours
  9306     B/M0000000    NETFINITY RACK            B/M76H4949   00.7     00.2


PHYSICAL CHECK:


PREREQUISITES: NONE

COMPANION: NONE

CONCURRENT: NONE


DETAIL:

IBM Quality has determined that a limited number of side panel Options for 9306-900 Racks fit improperly to the Rack assembly due to incorrect panel-to-rack latch bracket welds.

To determine if you have good covers upon visual inspection, the measurement from the bottom of the cover to the bottom of the tab that rest on the frame must be 35mm +/- 1mm.

Note: If the dimension is in the 16-18mm range you have a defective cover.
Order a new cover, FRU P/N 76H4949, using Code "B".

Note: All FRU Stock in Amsterdam and Mechanicsburg have been checked and are not effected.

NOTES:

This ECA is NOT mandatory.
This ECA is scheduled to be withdrawn April 30, 2000.

Parts in "Features" Section, under "B/M to be Installed" column, should be Ordered Code "B".

PARTS DISPOSITION:

The removed parts are the property of IBM and should be removed from the account.
Dispose of them per your country guidelines and local branch office procedures.

USA:
IBM PSS/TSS CE's should record all time and parts to Service Code 33, ECA030, Other Office 990.
Travel Time = 0.8Hrs.

USA Business Partners: Warranty claims for ECA Reimbursement should be submitted via ECLAIM using Type Service 0E. Refer to the Service Support Guide (SSG) for details.


EMEA:
IBM PSS CE's should record all time and parts to Service Code 33, ECA030, (M/T9306) Other Office 990.
Travel Time = 0.8Hrs.

EMEA Business Partners: Refer to Warranty Claim System; Use Emergency Claim 5 (ECA) and enter into CPPS:
ECA Number 030
Machine Type 9306.


Back to  Jump to TOP-of-PAGE

Please see the LEGAL  -  Trademark notice.
Feel free - send a Email-NOTE  for any BUG on this page found - Thank you.